{"id":3255,"date":"2020-03-02T18:25:01","date_gmt":"2020-03-02T18:25:01","guid":{"rendered":"http:\/\/www.cofem.com\/product\/modulo-kmay32\/"},"modified":"2022-03-17T11:44:56","modified_gmt":"2022-03-17T11:44:56","slug":"kmay32-module","status":"publish","type":"product","link":"https:\/\/www.cofem.com\/en\/product\/kmay32-module\/","title":{"rendered":"KMAY32 MODULE"},"content":{"rendered":"

KMAY32 MODULE TO CONNECT 32 DETECTORS \/ 10 ALARM CALL POINTS<\/h2>\n<\/div><\/div><\/div><\/div><\/div><\/div><\/div><\/section>
\"\"<\/div><\/div><\/div><\/div><\/div>

Microprocessed and algorithmic-addressable module (with short-circuit insulator) which is installed as one more element in the loop.<\/p>\n

This module allows the connection of conventional detectors and\/or alarm call points in an algorithmic-addressable fire detection system, performing the interface function between an algorithmic-addressable control panel and a conventional system. Up to a maximum of 10 conventional alarm call points can be installed on the strip of \u201cArea C\u201d. The \u201cD Area\u201d strip allows a maximum of 32 temperature detectors (A30XT, A30XV) or 32 components between smoke detectors (A30XH, A30XHS) and conventional alarm call points. Both strips supervise the line using a 4K7 end-of-line resistor. It thus indicates the status of the open line, crossed line, detector alarm or alarm call point alarm.<\/p>\n<\/div><\/div><\/div><\/div><\/div><\/div><\/div><\/section>

Features<\/h6>\n

It has a microswitch for setting the area thresholds;<\/p>\n